Описание

  • Usage up to category 4 according to EN ISO 13849-1
  • Requirement level IIIC according to EN 574
  • LED status indicators
  • Operation using 2-hand control
  • 2 redundant safety contacts
  • Short-circuit and earth fault/ground fault monitoring can be selected
Relay outputsThe outputs are electrically decoupled and of redundant design. Connection
  • Two buttons each with one normally closed contact and one normally open contact that are monitored for simultaneity according to EN 574. In this way a high level of protection against tampering is provided.
  • Short circuit monitoring to detect short circuits between the connection cables and to shut down the outputs or prevent relay starting if necessary
  • Earth fault/ground fault monitoring to detect short circuits between the connection cables and earth or ground and to shut down the outputs or prevent relay starting if necessary.
Connection optionsBy using suitable wiring the following function can be selected:
  • Monitoring of downstream relays or contactors
Dimension drawing Wiring diagram Dimension drawingWiring diagram Technical dataApprovals Mechanical values and environment
Housing material Polyamide PA6.6
Weight
Net 0,23 kg
Ambient temperature
At UB = 24V DC -15 ... 60 °C
At UB = 24V AC -15 ... 40 °C
Degree of protection IP20
Mechanical life
operating cycles 10 x 106
Contact material AgSnO2
Mounting method Mounting rail 35mm according to DIN EN 60715 TH35
Connection Connection terminals
Length of control cable
With conductor cross-section 0.75mm2 1000 m
Safety contacts 13/14, 23/24
Number of safety contacts 2
Electrical connection ratings
Operating voltage
AC/DC 24 V -10% ... +10%
Rated insulation voltage Ui 250 V
Rated impulse withstand voltage Uimp
Leakage path/air gaps 4 kV
Overvoltage category according to IEC EN 60664-1 3
Reverse polarity protection
On version UB =24V DC
Power consumption
at 24V DC 1,5 W
Degree of contamination (external, according to EN 60947-1) 2
Connection cross-section 0,14 ... 2,5 mm? Connection terminal (size)
Test voltage
Control system/contacts 2,5 kV
Control voltage
On S12-S13 and on S22 and S23 24 V
Control current
Both push buttons 40 mA 2x
LED indicator 2 status displays (green) for relays K1 and K2
Safety contacts 13/14, 23/24
Type of output
NO Relay contacts, floating and positively driven (redundant)
Switching voltage
DC max.24 V
AC max.250 V
Switching current min.20 mA at 24V
Fusing
External contact fuses (safety circuit) according to IEC 60269-1 10A gG (T6A / F8A)
Utilization category according to EN 60947-5-1
AC-15 3A, 250V
DC-13 3A, 24V
AC-12 6A ohmic load, 250V
DC-12 6A ohmic load, 24V
Breaking capacity according to UL 6A 250V AC / 2A 24V DC
Delay time
After operation of the push buttons max.0,02 s Response delay time
Release time max.0,02 s
Synchronization time max.0,5 s
Other
In compliance with EN 60439-1: 1999 + A1: 2004, EN 60947-1: 2007, EN 60947-5-1: 2004, EN 60947-7-1: 2002, EN 61000-6-2: 2005, EN 61000-6-3: 2007, EN ISO 13849-1: 2015, EN 62061: 2005 + AC: 2010 + A1: 2013 + A2: 2015, EN 60204-1: 2007
Reliability values according to EN ISO 13849-1
Performance Level PL e
Category 4
PFHD 1.2 x 10-8
Number of switching cycles
? 0.1 A at 24 V DC max.400000 1/Jahr
? 1 A at 24 V DC max.100000 1/Jahr
? 3 A at 24 V DC max.22500 1/Jahr
Mission time 20 y
''